This bolted separable tee connector allows cables to be connected together. It is suitable for electrical system rated smaller than 24kV. The Tee connector links cables to interface C bushings, like ring main units, cable branch boxes, transformers and switchgears, which ensures insulation and forms a ring power network. It is made of EPDM and an insulation layer will be moulded between the insert and the jacket after being connected to epoxy-resin-coated cables.
Ordering instruction
The ordering formula as followed:
| 1 | 2 | 3 | 4 | |
| WEB |
Step 1
Choose the system voltage and current: 24/630.
Step 2
Select the range from Table D that fits the diameter over cable insulation.
Step 3
Select the conductor code from Table C for the conductor size and type.
Step 4
Select the package. 1: 1pc/kit; 3: 3pcs/kit.
Table D
Diameter over cable insulation
| Insulation Range Code | Diameter over cable insulationφ(mm) | |
| Min. | Max. | |
| A* | 16 | 19 |
| A | 19 | 22 |
| B | 22 | 25 |
| C | 25 | 28 |
| D | 28 | 32 |
| E | 32 | 35 |
| F | 35 | 38 |
| G | 38 | 41 |
| H | 41 | 42.5 |
Table C
Conductor Code
| Conductor Cross-section (mm²) | Copper Lug (Hexagonal compression) |
| 25 | 01C |
| 35 | 02C |
| 50 | 03C |
| 70 | 04C |
| 95 | 05C |
| 120 | 06C |
| 150 | 07C |
| 185 | 08C |
| 240 | 09C |
| 300 | 10C |
| 400 | 11C |
Ordering example:
The cable is 24kV, 3-core 95mm² copper conductor with core insulation diameter of 24mm. Order WEB 24/630B05C3.
Note:
Sealing or solderless grounding kits shall be ordered separately.
Insulated plug with capacitive test point is available upon request.
Please add "-X" for cable with copper wire shield without armour, like WEB 24/630D05C3-X.
Feel free to contact us for detailed information.
Technical Data
| Voltage Class | 24kV | |
| Continuous Current | 630A | 1250A* |
| AC Withstand Voltage | 54kV for 5 min | |
| Partial Discharge | 20kV, ≤10pc | |
| Impulse Withstand Voltage (10 times for each polarity) | 125kV | |
| Screen Resistance | ≤5000Ω | |
| Screen Fault Current Initiation | For solidly/unearthed /impedance earthed system | |
Note: * refer to the condition when installed on an appropriate equipment bushing.
Pass all factory tests.
Meet the requirements of GB/T12706.4, HD629.1 and IEC60502-4 of separable insulated connectors.
Obtain a formal test report issued by a third-party laboratory.