The medium voltage 1-core Indoor Cold Shrink Termination is an indoor terminal processing accessory for medium voltage cable systems (usually voltage levels of 6kV to 35kV), specially designed for single core cables. It uses cold shrink technology, and when installing, the support tube is pulled out to automatically shrink the material, tightly wrapping the cable terminal, providing reliable electrical insulation, mechanical protection and environmental sealing.
| Voltage U0/U(Um) | Cores | Cable Cross Section /mm² | Nominal insulation thickness/mm | Diameter over Insulation/mm | Kit No. |
| 6/10(12)kV 6.35/11(12)kV | 1,3 Indoor | 25-35 50-70 95-150 185-300 400-500 630 | 3.4 | 13.5-16 16-19.5 19-24.5 23.5-30 30.5-35 37-42.3 | 12kVWLN- 1/0(3/0) 12kVWLN- 1/1(3/1) 12kVWLN- 1/2(3/2) 12kVWLN-1/3(3/3) 12kVWLN-1/4(3/4) 12kVWLN-1/5(3/5) |
| 1,3 Outdoor | 25-35 50-70 95-150 185-300 400-500 630 | 3.4 | 13.5-16 16-19.5 19-24.5 23.5-30 30.5-35 37-42.3 | 12kVWLW- 1/0(3/0) 12kVWLW- 1/1(3/1) 12kVWLW- 1/2(3/2) 12kVWLW- 1/3(3/3) 12kVWLW- 1/4(3/4) 12kVWLW- 1/5(3/5) | |
| 8.7/15(17.5)kV | 1,3 Indoor | 16 25-50 70-120 150-240 300-400 500-630 | 4.5 | 13.5-16 16-19.5 19-24.5 23.5-30 30.5-35 37-42.3 | 17.5kVWLN- 1/0(3/0) 17.5kVWLN- 1/1(3/1) 17.5kVWLN- 1/2(3/2) 17.5kVWLN- 1/3(3/3) 17.5kVWLN-1/4(3/4) 17.5kVWLN-1/5(3/5) |
| 1,3 Outdoor | 16 25-50 70-120 150-240 300-400 500-630 | 4.5 | 13.5-16 16-19.5 19-24.5 23.5-30 30.5-35 37-42.3 | 17.5kVWLW- 1/0(3/0) 17.5kVWLW- 1/1(3/1) 17.5kVWLW- 1/2(3/2) 17.5kVWLW- 1/3(3/3) 17.5kVWLW-1/4(3/4) 17.5kVWLW-1/5(3/5) | |
| 12/20(24)kV 12.7/22(24)kV | 1,3 Indoor | 25-50 70-120 150-240 300-400 500-630 | 5.5 | 18-21.5 21-26.5 25.5-32 32.5-37 39-44.3 | 24kVWLN-1/1(3/1) 24kVWLN-1/2(3/2) 24kVWLN-1/3(3/3) 24kVWLN-1/4(3/4) 24kVWLN-1/5(3/5) |
| 1,3 Outdoor | 25-50 70-120 150-240 300-400 500-630 | 5.5 | 18-21.5 21-26.5 25.5-32 32.5-37 39-44.3 | 24kVWLW-1/1(3/1) 24kVWLW-1/2(3/2) 24kVWLW-1/3(3/3) 24kVWLW-1/4(3/4) 24kVWLW-1/5(3/5) | |
| 18/30(36)kV 19/33(36)kV | 1,31 Indoor | 35-50 70-95 120-185 240-500 630 | 8.0 | 22-27 27-30 30-35 35.5-46 46.5-55 | 36kVWLN-1/1(3/1) 36kVWLN-1/2(3/2) 36kVWLN-1/3(3/2) 36kVWLN-1/4(3/3) 36kVWLN-1/5(3/4) |
| 1,3 Outdoor | 35-50 70-95 120-185 240-500 630 | 8.0 | 22-27 27-30 30-35 35.5-46 46.5-55 | 36kVWLW-1/1(3/1) 36kVWLW-1/2(3/2) 36kVWLW-1/3(3/2) 36kVWLW-1/4(3/3) 36kVWLN-1/5(3/4) | |
| 20.8/36(42)kV | 1,3 Indoor | 50-95 120-240 300-400 500-630 | 9.3 | 28.5-35 35.5-42 42.5-48 48.5-56 | 42kVWLN-1/1(3/1) 42kVWLN-1/2(3/2) 42kVWLN-1/3(3/3) 42kVWLN-1/4(3/4) |
| 1,3 Outdoor | 50-95 120-240 300-400 500-630 | 9.3 | 28.5-35 35.5-42 42.5-48 48.5-56 | 42kVWLW-1/1(3/1) 42kVWLW-1/2(3/2) 42kVWLW-1/3(3/3) 42kVWLW-1/4(3/4) | |
| 26/35(42)kV | 1,3 Indoor | 50-95 120-240 300-400 500-630 | 10.5 | 28.5-35 35.5-42 42.5-48 48.5-56 | 42kVWLN-1/1(3/1) 42kVWLN-1/2(3/2) 42kVWLN-1/3(3/3) 42kVWLN-1/4(3/4) |
| 1,3 Outdoor | 50-95 120-240 300-400 500-630 | 10.5 | 28.5-35 35.5-42 42.5-48 48.5-56 | 42kVWLW-1/1(3/1) 42kVWLW-1/2(3/2) 42kVWLW-1/3(3/3) 42kVWLW-1/4(3/4) |
Applicable voltage level: Applicable to medium voltage cable systems from 6kV to 35kV.
Number of cores: Designed specifically for single core cables.
Cold shrink technology: No heating required, automatic shrinkage by elastic material, easy installation.
Material properties: Usually silicone rubber or ethylene propylene rubber (EPDM) is used, with good insulation performance, weather resistance and mechanical strength.
Environmental adaptability: Suitable for indoor environment, with good waterproof and moisture-proof performance.